Foam compound  delivery rates in accordance with
DIN 14 493 Sections 1-4
for stationary/  foam fire extinguishing installations

Fire extinguishing installation

Low-
expansion
foam

Medium-
expansion
foam

High-
expansion
foam

Object

Water flow rate in
litres / minute  & /m²
**

Desired flooding
time in min., ER > 200
**²

Fire class A

 

 

 

-Materials with a low  density

 

4

-Materials with a high density

 

5

-Materials in  boxes/packaging

 

6

-Plastics, tyres, bulk materials

 

6

 

 

 

 

Fire class B ¹

 

 

 

Flash  point < 55°C

 

3

Flash point >55°C

 

4

 

 

 

 

Fixed  cover tanks
 Ø< 20 m also with floating cover

6.6

3

 

 

 

 

 

Fixed  cover tanks
Ø > 20 m

6.6 + 0.2

3 + 0.2

 

 

 

 

 

Floating cover tank with annular gap
foam delivery

6.6

2

 

 

 

 

 

Collecting area with
with vertical  container

3.3

 

 

 

 

 

 

Collecting area with
with horizontal container

6.6

 

 

 

 

 

 

Tanks  and collecting areas
for polar fluids

6.6 + X *

Water flow
rate x X
*

 

 

 

 

 

¹

Does not apply to hydrophilic fluids

²

Additional calculation factors must /be  taken into account to determine the foam compound requirement for high-expansion foam fire extinguishing installations.

*

If necessary, tests must be carried out to determine the increase in the water flow rate due to the des! truc tion of foam by the
polar  fluid.

**

The  foam compound consumption in litres / minute is calucated from the water flow  rate in litres per minute and the addition percentage.